3Ć61 Theory of Operation: Self Test
Original Ć June 1990
CE4.2:CL6211
3.7.8 Recommended Minimum Free Time Value
The user should take precautions to assure that the controller free time
(loading) is never reduced below 20 percent free time. This idle time is
required to take care of the processor computations required under burst
load conditions. A burst load can be induced by many conditions, such
as the following:
H Communications load, such as asynchronous requests on multiple
communications channels happening to coincide in time.
H Controller tracking operations, which may require extra computations
internally to balance the control algorithms.
H Diagnostic and/or Tuning operations, which cause the controller to
perform extra computations concurrent with normal control algorithms.
H FST branching, where the user configuration may under certain
circumstances perform extra steps during a brief transition period.
Note that the simple fact that less than 20 percent free time has been
computed by the controller will NOT cause an integrity error to be
reported, (unless it should happen to have forced the FST execution to
exceed the FST scan rate, which would force an FST overload to be
signalled). Therefore, as part of the system configuration and
commissioning, the configuration engineer should insure that the
controller loading requirements have been met.