4Ć60 FST Configuration
Original Ć June 1990CE4.2:CL6211
DI DI
21
INSTRUCTION NAME: DI (discrete input)
DESCRIPTION : This instruction sets the SVD output equal to logic 1 when the value of the SVD
input, at the channel specified by operand 1, is between 0 and 1 volt dc across the discrete input
terminals. When the SVD input value is between 4 and 28 volts dc across the terminals, the SVD
logic output is 0. The SVA input remains unchanged.
GRAPHIC REPRESENTATION: SYMBOLIC REPRESENTATION:
0 VDC
INPUT
1
0
OUTPUT
t
0
t
1
t
2
t
0
t
1
t
2
28 VDC
DI
4VDC
CONFIGURATION FORMAT: DI (
DI channel >>
Comment >>
OPERAND DESCRIPTIONS:
DI channel - The channel number of the desired discrete input. The type and number of inputs for
each controller is as follows:
Field wiring
Controller type Terminal designation DI channel number
Computing DI1 to DI4 1 to 4
2-Wide DI1 to DI4 1 to 4
3-Wide Discrete DI1 to DI4 1 to 4
3-Wide Analog DI1 to DI4 1 to 4
4-Wide DI1 to DI8 1 to 8
Comment - A comment up to 255 characters long.
(Continued on next page)