4Ć130 FST Configuration
Original Ć June 1990CE4.2:CL6211
OVRD OVRD
70
INSTRUCTION NAME: OVRD (override)
DESCRIPTION:
This instruction causes the output of the station function (STAT) to perform
either output or integral tracking. When the value in operand 3 is 1, the STAT function output tracks
the value in operand 2. When the value in operand 3 is 0 and the value in operand 4 is 1, the STAT
function output performs integral tracking.
A controller in the AUTO, RSP, SUP, or DDC mode will perform output tracking if the value in
operand 3 is 1. A controller in manual mode will perform output tracking when operand 1 is enabled
and operand 3 is 1. (Normal manual mode operation will occur if operand 1 is disabled.) Output
tracking sets the output of the STAT function equal to the track value in operand 2.
A controller in the AUTO, RSP, or SUP mode will perform integral tracking when the value in
operand 3 is 0 and integral tracking is enabled (operand 4 = 1).
Note
To avoid loop windup in override control applications
for which integral tracking (operand 4) is enabled,
place a FIL function and a RGST function immediately
after the AOUT function of the loop containing the
signal selecting operation. The name of the general
register used by the RGST function is then specified in
operand 2 of the OVRD function.
Refer to section NO TAG (page NO TAG) for
instructions on determining the correct filter time
constant.
The OVRD function must precede the CNTRL function in the FST and cannot be used in the same
loop in conjunction with a cascade, track, or another override function. The SVA and SVD inputs
remain unchanged.
(Continued on next page)