Response Electronics CL6011B Spécifications Page 191

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 320
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 190
4Ć109FST Configuration
Original Ć June 1990 CE4.2:CL6211
INT INT
(Continued from previous page)
OPERAND DESCRIPTIONS:
Integrator gain - A tuning parameter value in units of repeats per minute. The gain is any
non-negative floating point number. For a constant input, the output will change by the input value
multiplied by the integrator gain per minute.
Initial condition - The name of the general register or analog loadable function that contains the
analog value used as the SVA output when the value in operand 3 is 1.
Reset signal - The name of the general register or discrete loadable function that contains the
reset value. (Logic 0 = normal integration, logic 1 = reset to initial value specified in operand 2)
Comment - A comment up to 255 characters long.
CONFIGURATION EXAMPLE: INT (2.9, AIN (1), DI (1))
FUNCTION EQUATIONS:
If Reset signal = 0,
Then SVA(out) = HA + [(TP X
Dt) X SVA(in)]
Where: HA = SVA(out) last cycle
TP = Integrator gain in repeats per minute (operand 1)
Dt = Sample time in minutes
If Reset signal = 1,
Then SVA(out) = Analog value in operand 2
SVD(out) = SVD(in)
On power up:
SVA(out) = HA = Analog value in operand 2
SVD(out) = SVD(in)
Vue de la page 190
1 2 ... 186 187 188 189 190 191 192 193 194 195 196 ... 319 320

Commentaires sur ces manuels

Pas de commentaire