3Ć28 Theory of Operation: Point Processing
Original Ć June 1990CE4.2:CL6211
3.3.3.3.3 Watchdog Timer
Watchdog timer allows the direct control point to be placed in a specified
backup mode if an update from a console or computer is not received
before the specified time interval and the watchdog timer alarms. It can
only be used with a station type that supports SUP or DDC modes.
3.3.3.4 Functions Common to Primary Control Algorithm and Station
Both the primary control algorithm and the station contain some
functions that are common in theory. These functions are restart values
and set point tracking which are described in the following sections.
3.3.3.4.1 Restart Values
There are several direct control point parameters that have configurable
restart values that may be used if the controller is restarting from a power
failure or a download. In addition to the restart values, the parameters
may also restart from the last value established before a shutdown of the
controller. The parameters which have configurable restart values are the
Set Point (SP), the Implied Valve Position (IVP), the operating mode
(MODE), the bias (BI), and ratio. Indirect Control Point (ICP) reference
values will automatically restart at the last value when a power failure
occurs.
Restart Value Storage
The restart values are retained in non-volatile memory (NVM). Power
fail restart will recall these values from NVM. The restart from last values
are updated in NVM once a minute if the values have changed
significantly. The required amount of change before the NVM value is
updated is 5% of span for set point, bias, IVP and ICP reference values.
The required amount of change before the NVM value is updated is an
absolute change of 0.12 for the ratio value. Mode is updated upon any
change.
Restart After a Power Failure
After a power failure, when restart from last value is specified, the restart
parameters are set to the last value established before the power failure.
When a specific restart value is defined, that value is used as the restart
value after power failure.