4Ć79FST Configuration
Original Ć June 1990 CE4.2:CL6211
FDFWS FDFWS
(Continued from previous page)
OPERAND DESCRIPTIONS:
Summer enable - A tuning parameter that enables or disables the summing input (operand 8).
(YES = enable, NO = disable).
Summer gain - A tuning parameter that determines the summer gain. Gain values are from 0 to
10.00.
Summer REV/DIR - A tuning parameter that affects the polarity of the summer input (operand 4).
(DIR = no change, REV = change sign).
Summer value - The name of the general register or analog loadable function that contains the
analog value (in percent) for the summer input.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
If operand 1 = YES, and operand 3 = DIR
Then SVA(out) = SVA(in) + (operand 2 X operand 4)
If operand 1 = YES, and operand 3 = REV
Then SVA(out) = SVA(in) - (operand 2 X operand 4) + 100
SVD(out) = SVD(in)