Response Electronics CL6011B Spécifications Page 207

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 320
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 206
4Ć125FST Configuration
Original Ć June 1990 CE4.2:CL6211
MIDSEL MIDSEL
(Continued from previous page)
OPERAND DESCRIPTIONS:
Mid-selector range - This tuning parameter specifies the acceptable range (dead band)
between values. Dead band values are any non-negative floating point number.
Second input - The name of the general register or analog loadable function that contains the
second input.
Third input - The name of the general register or analog loadable function that contains the third
input.
Comment - A comment up to 255 characters long.
FUNCTION EQUATIONS:
SVA(out) = middle value [SVA(in), second input, third input]
If ((highest value - middle value) > dead band) OR
((middle value - lowest value) > dead band)
Then SVD(out) = 1
Else
SVD(out) = 0
Where: dead band = operand 1
second input = operand 2
third input = operand 3
Vue de la page 206
1 2 ... 202 203 204 205 206 207 208 209 210 211 212 ... 319 320

Commentaires sur ces manuels

Pas de commentaire