4-43Input and Output Cards
Original — December 1991 UM4.6:CS6003
Table 4-21. Momentary Output Duration Switch Settings for
DM6460-Series Discrete Output Cards (Continued)
Switch Positions for S13, S14, S16, S17, S33, S34,
S36, and S37
Required
Output
Durations
in Seconds
87654321
23.9 ON ON ON OFF ON ON ON ON
24.0 ON ON ON ON OFF OFF OFF OFF
24.1 ON ON ON ON OFF OFF OFF ON
24.2 ON ON ON ON OFF OFF ON OFF
24.3 ON ON ON ON OFF OFF ON ON
24.4 ON ON ON ON OFF ON OFF OFF
24.5 ON ON ON ON OFF ON OFF ON
24.6 ON ON ON ON OFF ON ON OFF
24.7 ON ON ON ON OFF ON ON ON
24.8 ON ON ON ON ON OFF OFF OFF
24.9 ON ON ON ON ON OFF OFF ON
25.0 ON ON ON ON ON OFF ON OFF
25.1 ON ON ON ON ON OFF ON ON
25.2 ON ON ON ON ON ON OFF OFF
25.3 ON ON ON ON ON ON OFF ON
25.4 ON ON ON ON ON ON ON OFF
25.5 ON ON ON ON ON ON ON ON
4.2.3 Types DM6461, DM6462, and DM6463 Discrete Output
Cards
The field wiring from the Type DM6462 and Type DM6463 Discrete
Output Cards requires special consideration because these wires
typically carry high voltages (115 to 240 volts ac) or high switched
currents (up to 10 amperes). For this reason, consider these wires as ac
power lines, and maintain physical separation between field wiring for
these cards and the other I/O cards. For long runs, bring field wiring to a
junction box and then route through multipair shielded cable.
4.2.3.1 Discrete Output to External Field Device Connections
The field wiring information for these boards is located in the planning
manual: Installing Type CP6601 Input/Output File (PN4.4:CP6601).