4-2 Input and Output Card
UM4.6:CS6003 Original — December 1991
X00605–A
R7 Span Adjustment R8 Zero Adjustment
OLD STYLE
R11 Zero Adjustment R15 Span Adjustment
NEW STYLE
Figure 4-1. Single-Ended Analog Input Card
4.1.1.2 Equipment Required
The following equipment is required:
Type CS6003 Calibrator
Voltage Source
4.1.1.3 Calibration Procedure
Use the following procedure to calibrate the card:
Step 1: Verify that the calibrator ON/OFF switch is OFF.
Step 2: Insert the single-ended analog input card into the calibrator
test slot labeled MUX.
4